电器与能效管理技术 ›› 2024, Vol. 0 ›› Issue (11): 58-64.doi: 10.16628/j.cnki.2095-8188.2024.11.007

• 储能技术 • 上一篇    下一篇

基于有源阻尼控制算法的125 kW PCS在并网运行下多机并联系统谐振的抑制方法

吴世超1, 李靖1, 郑燕波2   

  1. 1.温州大学 电气与电子工程学院, 浙江 温州 325035
    2.浙江创奇新能源科技有限公司, 浙江 嘉兴 314019
  • 收稿日期:2024-09-05 出版日期:2024-11-30 发布日期:2024-12-11
  • 作者简介:吴世超(2000—),男,硕士研究生,研究方向为储能变流器电能质量分析。|李 靖(1967—),男,教授,博士,研究方向为储能变流器技术。|郑燕波(1983—),男,高级工程师,主要从事储能变流器研发工作。

Multi-Machine Parallel Resonance Suppression Method of 125 kW PCS in Grid-Connected Operation Mode Based on Active Damping Control Strategy

WU Shichao1, LI Jing1, ZHENG Yanbo2   

  1. 1. College of Electrical and Electronic Engineering,Wenzhou University, Wenzhou 325035, China
    2. Zhejiang Chuangqi New Energy Technology Co.,Ltd., Jiaxing 314019, China
  • Received:2024-09-05 Online:2024-11-30 Published:2024-12-11

摘要:

基于当下市场流行的125 kW PCS模块,考虑电网阻抗因素,对并网运行模式下单个PCS和多机并联的PCS系统进行数学建模和阻抗分析,研究其在并网运行模式下多机并联谐振的抑制方法。从公共连接点分析多台PCS并联系统的系统侧阻抗,并应用叠加原理分析并网电流的变化,发现电网的线路阻抗与PCS相互耦合是引起系统谐振问题的关键。分析无源阻尼的谐波尖峰抑制,提出一种通过优化电容电流采样反馈环节来提供虚拟阻尼的有源阻尼控制策略。最后,通过Simulink仿真进行验证分析,结果表明采用有源阻尼控制策略的125 kW PCS多机并联系统在并网运行模式下,总谐波畸变率(THD)从9.67%降至2.02%,并网电流谐振尖峰受到很好的抑制。

关键词: 储能变流器, 并网运行, 多机并联, 谐振, 有源阻尼

Abstract:

Based on the popular 125 kW power conversion system (PCS) module in the current market,considering the grid impedance factor,the mathematical modeling and the impedance analysis of a single energy storage PCS and a multi-machine parallel PCS system in the grid-connected operation mode are implemented.The suppression method of multi-machine parallel resonance in the grid-connected operation mode is studied.The system side impedance of multiple PCS parallel systems is analyzed from the point of common connection,and the change of grid-connected current is analyzed by superposition principle.It is found that the coupling between the line impedance of the power grid and PCS is the key to the resonance problem of the system.The harmonic peak suppression of passive damping is analyzed,and an active damping control strategy is proposed to provide virtual damping by optimizing the capacitor current sampling feedback link.Finally,the simulation is carried out by Simulink.The results show that the THD is reduced from 9.67 % to 2.02 % under the grid-connected operation mode of 125 kW PCS multi-machine parallel system with active damping control strategy,and the resonance peak of grid-connected current is well suppressed.

Key words: power conversion system (PCS), grid-connected operation, multi-machine parallel connection, resonance, active damping