电器与能效管理技术 ›› 2026, Vol. 0 ›› Issue (10): 29-34.doi: 10.16628/j.cnki.2095-8188.2026.10.004

• 电弧检测与研究 • 上一篇    下一篇

可编程控制电弧故障发生系统的研究

褚若波1, 陆接民1, 林圻斌2, 杨凯2   

  1. 1 泉州师范学院 物理与信息工程学院, 福建 泉州 362000
    2 华侨大学 机电及自动化学院, 福建 厦门 361021
  • 收稿日期:2026-06-02 出版日期:2026-10-30 发布日期:2026-11-20
  • 作者简介:褚若波(1991—),男,讲师,博士,研究方向为机电装备运行状态监测与诊断。|陆接民(2005—),男,研究方向为电弧故障检测。|林圻斌(1994—),男,硕士,研究方向为自动化检测装置开发。
  • 基金资助:
    福建省科技厅创新资金项目(2025C0010);泉州市高层次人才创新创业项目(2025QZC26R);福建省中青年教师教育科研项目(JAT251116)

Research on Programmable-Control Arc Fault Generation System

Chu Ruobo1, Lu Jiemin1, Lin Qibin2, Yang Kai2   

  1. 1 College of Physics and Information Engineering, Quanzhou Normal University, Quanzhou 362000, China
    2 College of Mechanical Engineering and Automation, Huaqiao University, Xiamen 361021, China
  • Received:2026-06-02 Online:2026-10-30 Published:2026-11-20

摘要:

电弧故障探测器(AFDD)是一种预防电弧型电气火灾的保护装置。由于电弧具有随机产生的电气特征,目前的AFDD性能测试平台不能有效产生数量可控的真实电弧故障。针对这一问题,根据电弧故障的国家判定标准,采用绝缘栅双极型晶体管(IGBT)设计驱动电路,控制电弧故障的产生,并采集电弧间电压信号,以电压积分验证实时电弧故障周期半波数,对AFDD的脱扣时间和报警时间进行测量,判断AFDD的动作性能是否达到国家标准的规定。试验结果表明:该系统能有效产生数量在20个以内、位置可控的真实电弧故障,计算出AFDD响应时间约在0.1 s,为AFDD的研究提供了可靠的设备支持。

关键词: 电弧故障, 绝缘栅双极型晶体管, 电压积分, 半波检测

Abstract:

Arc fault detection device (AFDD) is a protective device for preventing arc-induced electrical fires. Owing to the stochastic electrical characteristics of arcs, existing AFDD performance test platforms fail to effectively generate real arc faults with controllable quantities. According to the national criteria for arc faults, a drive circuit based on Insulated Gate Bipolar Transistor (IGBT) is designed to control the generation of arc faults. The voltage signal across the arc gap is collected, and voltage integration is adopted to verify the number of half-wave cycles of real-time arc faults. The tripping time and alarm time of AFDD are measured to judge whether its operating performance satisfies the requirements specified in national standards. Experimental results show that the system can stably generate real arc faults with controllable positions and a quantity of up to 20. The calculated response time of AFDD is approximately 0.1 s, and reliable test equipment support is provided for the research of AFDD.

Key words: arc fault, insulated gate bipolar transistor (IGBT), voltage integration, half-wave detection

中图分类号: