Calculation of Distance Protection Setting of Regional Power Grid Considering Traction Power Supply

CHEN Qidi1, NAN Dongliang1, FENG Xiaoping2, WANG Wenhuan3, ZHANG Lu1   

  1. 1. Electric Power Research Institute State Grid Xinjiang Electric Power Co.,Ltd., Urumqi 830000, China
    2. State Grid Xinjiang Electric Power Co.,Ltd., Urumqi 830000, China
    3. China Electric Power Research Institute, Beijing 100192, China
  • Received:2020-09-17 Online:2020-12-30 Published:2021-01-13

Abstract:

Due to the asymmetry of the traction load,there is a problem in the calculation of the measured impedance when the line distance protection on the grid side cooperates with the traction transformer,which brings the puzzle to the setting calculation personnel whether the distance protection can avoid the faults on low side of the traction transformer.The influence of traction substation on distance protection is analyzed.The analysis models of single-phase Ii traction transformer,V/v wiring traction transformer and V/x wiring traction transformer are built.The measurement impedance correction scheme of the grid side distance protection after low side of the traction transformer being faulty is analyzed.The setting calculation suggestions for the distance protection are provided.

Key words: traction transformer, distance protection, measured impedance, setting calculation