LOW VOLTAGE APPARATUS ›› 2025, Vol. 0 ›› Issue (7): 44-48.doi: 10.16628/j.cnki.2095-8188.2025.07.007

• Electrical Design & Discussion • Previous Articles     Next Articles

Contact Failure Analysis and Optimization Design of Molded Case Circuit Breaker

LIU Haibin1, XIANG Xiaoqing2, ZHOU Mingming1   

  1. 1. Dalian Shipbuilding Industry Co.,Ltd., Dalian 116019, China
    2. Shanghai Electric Apparatus Research Institute (Group) Co.,Ltd., Shanghai 200063,China
  • Received:2025-05-27 Online:2025-07-30 Published:2025-08-27

Abstract:

A short-circuit overload test under an effective current of 8 000 A is conducted on a certain double-break moulded case circuit breaker (MCCB),and the contact ablation fault that occurred is analyzed. First, a theoretical calculation of the electric force is performed. Then, using Maxwell 3D finite element analysis software combined with the Holm force calculation formula,the electric repulsion of the double-break MCCB is calculated. The trends of the two calculation results are consistent, and the cause of contact ablation is determined through comparison.The error between the simulation calculation result and the measured value of contact pressure does not exceed 8%,and the used calculation method can provide a reference for the design and optimization of the MCCB contact system.

Key words: molded case circuit breaker (MCCB), finite element analysis, electrodynamic force, electromagnetic repulsion force, contact