LOW VOLTAGE APPARATUS ›› 2024, Vol. 0 ›› Issue (9): 24-28.doi: 10.16628/j.cnki.2095-8188.2024.09.004

• Research & Analysis • Previous Articles     Next Articles

Research on Influence of Installation Methods of Non Nnuclear Battery Cabinets on Seismic Performance

HAN Shuai1, LIANG Xiao1, RUAN Shanfa2, CHU Wenting2   

  1. 1. Daya Bay Nuclear Power Operation and Management Co., Ltd., Shenzhen 518124, China
    2. Hohai University, Nanjing 210098, China
  • Received:2024-04-24 Online:2024-09-30 Published:2024-10-16

Abstract:

Electrical equipment installation is generally categorized into bolt connections and welding.In order to verify the influence of the two installation methods on the seismic performance, two identical battery cabinets are fixed on the vibration table with various installation methods for seismic test.The test results show that the acceleration response of the welded cabinet is greater than that of the bolted cabinet, with higher resonance frequency, smaller displacement of the cabinet, larger overall stiffness, and greater stress of the welding part.However, bolted cabinets are prone to fastening failure of bottom beams, large battery and cabinet deformation and high stress due to torque.To improve the seismic performance of cabinets,the necessary measures need to be taken to reduce the cabinet deformation and collisions between batteries and cabinets.It is recommended to install battery cabinets with large mass and high center of gravity in full welding approach to reduce the impact of geometric deformation on the seismic performance of battery cabinets.

Key words: nuclear power plant, battery cabinet, response spectrum, seismic waves, seismic capability assessment

CLC Number: