Abstract:

Aiming at the time parameter detection of HV circuit breaker,a detection method is proposed.According to the characteristics of the coil current during the circuit breaker operation,the compensation Hall current sensor is selected,and the coil current signal is collected by FPGA.Then the current signal with noise is denoised by wavelet.Finally,the state change of the auxiliary contact is used to determine the time point of just opening (just closing) and the time of opening and closing,and the measurement results are within the allowable error range.

Key words: HV circuit breaker, current signal of switching coil, FPGA, wavelet denoising, extraction of characteristic parameters