LOW VOLTAGE APPARATUS ›› 2023, Vol. 0 ›› Issue (4): 21-27.doi: 10.16628/j.cnki.2095-8188.2023.04.004

• Arc Research & Analysis • Previous Articles     Next Articles

Research on Presure and Temperature Characteristics of Fault Arcing in GIS

WANG Zhining, PENG Haibo, ZOU Shun   

  1. Wuhan Inistiute of Marine Electric Propulsion,WuHan 430064, China
  • Received:2023-01-03 Online:2023-04-30 Published:2023-05-09

Abstract:

In order to reduce the frequency of arcing fault in gas insulated switchgear (GIS) and reduce the harm caused by arcing fault,according to the parameters of ZF32-126 GIS,the influence of internal fault arcing on gas itself is considered on the basis of standard pressure and temperature calculation model,and an improved calculation model is adopted.The thermodynamic parameters of SF6 under the fault arcing are calculated.On this basis,the thermodynamic parameters of SF6 are applied to the calculation model of pressure and temperature.When the internal fault current is 40 kA,the pressure and temperature rise characteristics of each gas chamber in ZF32-126 GIS,the maximum ablation degree and average ablation rate of the shell under different protection time are obtained,which verifies that the improved standard algorithm has higher accuracy.

Key words: gas insulated switchgear(GIS), calculation method, arcing fault, thermodynamic parameters, ablation