DIANQI YU NENGXIAO GUANLI JISHU ›› 2020, Vol. 589 ›› Issue (4): 89-92.doi: 10.16628/j.cnki.2095-8188.2020.04.016

• Power Quality • Previous Articles     Next Articles

Research on Drop Detection Method Adapted to Dynamic Voltage Recovery Control of Distribution Network

JIANG Hua1, BAI Jinhua1, SHEN Xinglai1, TENG Song1, HU Sheng2   

  1. 1.Xuzhou Power Supply Branch,State Grid Jiangsu Power Co.,Ltd.,Xuzhou 221000,China;
    2.Nanjing Institute of Technology,Nanjing 211167,China
  • Received:2019-12-29 Online:2020-04-30 Published:2020-04-30

Abstract: The problems of voltage sag detection of the industrial park distribution network after a large number of DGs were analyzed.The detailed design research based on the positive-negative sequence separation method of multi-dq coordinate rotation transformation and the S-transform method was carried out.Finally,in order to verify the correctness of the method,a simulation model was built in MATLAB/Simulink.The results show that the positive and negative sequence separation detection method based on multi-dq coordinate rotation transformation meets the real-time requirements of voltage recovery control,which lays a theoretical foundation for engineering design.

Key words: voltage sag, multi-dq coordinate rotation transformation, S-transform, dynamic voltage recovery