LOW VOLTAGE APPARATUS ›› 2023, Vol. 0 ›› Issue (1): 69-72.doi: 10.16628/j.cnki.2095-8188.2023.01.012

• Electrical Design & Discussion • Previous Articles     Next Articles

Analysis of Relay Contact Sticking Fault in Circuit Breaker Control System

SHI Jian, ZHOU Zhaoqing, YUE Feng   

  1. Guodian Nanjing Automation Co.,Ltd., Nanjing 211153, China
  • Received:2022-09-21 Online:2023-01-30 Published:2023-03-09

Abstract:

Electromagnetic relay is commonly used in tripping on/off a circuit breaker,where it can be used as a circuit holder.A case of the relay contact sticking fault found in the relay substitution test process is analyzed.It is demonstrated that the relay structure design caused more bounces and longer time after power on.The test shows that the relay bounce may lead to the contact sticking when the working current of tripping the circuit breaker closing coil is large.As a conclusion,the relay used in tripping on/off circuit breaker circuits shall check its bounce time and bounce count to avoid sticking problem.

Key words: circuit breaker, electromagnetic relay, contact bounce, contact sticking