LOW VOLTAGE APPARATUS ›› 2022, Vol. 0 ›› Issue (10): 44-47.doi: 10.16628/j.cnki.2095-8188.2022.10.007

• Electrical Design & Discussion • Previous Articles     Next Articles

Influence of Current Conditioning Process Parameters on Contact Surface Morphology in Vacuum Interrupter

XUE Feng, LI Min, LIN Liangwei, LIAO Qing   

  1. Schneider Electric (Xiamen) Switchgear Equipment Ltd.,Co., Xiamen 361006, China
  • Received:2022-01-28 Online:2022-10-30 Published:2023-01-04

Abstract:

In view of the influence of DC high current conditioning parameters on VI contact conditioning performance,the conditioning energy,contact stroke,synchronization between contact opening and capacitor discharge,arc injection mode and conditioning times on the coverage rate of vacuum arc abulation on contact surface are mainly studied.The results show that increasing conditioning energy,increasing contact stroke,adding low current striking arc and increasing conditioning times can improve contact conditioning effect.

Key words: current conditioning, vacuum interrupter, contact stroke, arc coverage