LOW VOLTAGE APPARATUS ›› 2022, Vol. 0 ›› Issue (2): 83-87.doi: 10.16628/j.cnki.2095-8188.2022.02.013
• Power Quality • Previous Articles Next Articles
SUN Lingxi, WANG Haixin, HUANG Haihong
Received:
Online:
Published:
Abstract:
Under the condition that the load of the grid is too large and the unbalance is high,the three-phase four-wire unbalance regulator had the phenomenon that the active compensation current exceeds the rated capacity of the equipment.The common method to solve this problem is to limit the amplitude,but this method can distort the active compensation current waveform and cause voltage fluctuations on the DC side of the equipment because the sum of the three-phase active currents flowing into the equipment is not zero.This paper introduces the working principle of the three-phase four-wire unbalance regulator,and analyzes the shortcomings of the limiting method,and finally proposes a new active current compensation scheme,i.e.,the active compensation current proportional reduction method.The correctness of this method is proved by mathematical derivation.Finally,it is verified through simulation and experiment that this method can avoid the drawbacks of the limiting method and maximize the regulating effect of the device.
Key words: three-phase four-wire unbalance regulator, active compensation current, limit amplitude
CLC Number:
TM761
SUN Lingxi, WANG Haixin, HUANG Haihong. New Algorithm for Three-phase Four-Wire Unbalance Regulators with Active Compensation Current Exceeding Capacity of Equipment[J]. LOW VOLTAGE APPARATUS, 2022, 0(2): 83-87.
0 / / Recommend
Add to citation manager EndNote|Ris|BibTeX
URL: http://www.eaes-seari.com/Jwk_dqynxgljs/EN/10.16628/j.cnki.2095-8188.2022.02.013
http://www.eaes-seari.com/Jwk_dqynxgljs/EN/Y2022/V0/I2/83